SCI ERV-24-HC11 Spezifikationen Seite 13

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 24
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 12
13
8.1 Set the fan cycling ON time and OFF time.
a. Press and hold the Select button until “LI” or ”UnLI” or ”CALC” appears on display.
b. Using the “+” and “-“ buttons select between:
“LI” – Fan cycling limited - default.
If “LI” is selected – no need to set “Fd” (Fan duty cycle) and “Ft” (Total
period).
“UnLI” – Fan cycling unlimited ON time.
Fan will be energized continuously after no fan activity for the fan OFF time.
“CALC” – Fan cycling calculated.
Fan cycling times will be calculated based on the fan duty cycle (“Fd”) and
total period (“Ft”).
If “CALC” is selected – go directly to 8.2 – no need to set “FO” (Fan cycling
limited ON time), “FF” (Fan cycling limited OFF time), “dO” (Damper cycling
OPEN time”) and “dC” (Damper cycling CLOSED time).
Seitenansicht 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 23 24

Kommentare zu diesen Handbüchern

Keine Kommentare